Troubleshooting the system                                       

                                                                 Unit does not start    

 Check thermostat     Turn fan to the on position if the furnace fan starts go check for power at the condensing unit.

Check disconnect , breaker or fuses.    Lets not forget about that switch at the bottom of the stairs.
Check Contactor    If the contactor is pulled in, then the problem is most likely a line voltage problem. If the contactor is not pulled in the           problem is in the low voltage side of the unit. Check to see if the coil is energized.
Check low ambient stat.     If open you can temporarily bypass it.
Check time delay relay    If open you can temporarily bypass it.
Is the low pressure control open ?    See low suction pressure. DO NOT BYPASS
Is the high pressure control open ?    See high head pressure. DO NOT BYPASS

                                                                        Insufficient Cooling
Check refrigerant charge    Either an undercharge or over charge can cause this.
 Is the condenser restricted ?    Look for leaves, paper ect.
Is the condenser clean ?    Clean it out with a garden hose. TURN OFF POWER FIRST. to clean it spray the water through the fins in the condenser.
Is there frost on the suction line ?    This is usually a sign of either loss of refrigerant charge or most commonly lack of air flow. See the next questions.
Are the filters plugged ?  result will be an extra cold suction line and low back pressure.
Is the evaporator clean ?  result will be an extra cold suction line and low back pressure.
Do you have sufficient air flow ?   result will be an extra cold suction line and low back pressure.
How many air diffusers are closed ?  Too many closed will result with extra cold suction line and low back pressure.
What is your Supply air temperature ?   Look for a TD of 15 to 20oF
Is the compressors drawing RLA ( rated load amps) or less ? If it's less are valves ok ? look for low head and higher than normal back pressure.

Over cooling
Check thermostat    Is it calibrated, sticking on or is it in an improper location.
Check the compressor contactor    Are the contacts welded closed

    Low head pressure
Check refrigerant charge for  Lack of refrigerant . DO NOT USE REFRIGERANT TO TRY TO INCREASE PRESSURE.
Out door air to low for proper operation    Normal units should not be run below 55oF without winter operation kits installed.
No load on the evaporator     Dirty filters, closed vents, dirty coils , incorrect fan speed , all will be noted with low back and possibly frost.
Compressor valve damage    Diagnosed by low head, high back and low current draw

                                                                   High head pressure
Check refrigerant charge  Overcharge will reduce the capacity of the condense  Is the condenser restricted ?    Look for leaves, paper ect.                 Is the condenser clean ?    Clean it out with a garden hose. TURN OFF POWER FIRST. to clean it spray the water through the fins in the condenser.                                                                                                                                                                                                      Does the fan motor seam to be running properly?   
Does the system have non condensable in it?    Sometimes noted by excessive subcooling or at least what appears to be according to a PT chart.       Is condenser air re circulating    unit under a deck or low roof                                                                                                                                                                                                                        

High suction  pressures                                                                                                                                               

Compressor Valve damage     look for low head pressure and low current draw.                                                                                                   Excessive high head pressure     resulting in increased pressure drop on metering device, refer to High head pressure.                                             Excessive Load  Furnace heat on     Unit too small       

                                                                                                                                                                                                               Low Suction Pressure                                                                                                                                                                                Is there frost on Check refrigerant charge    Either an undercharge or over charge can cause this.                                                                            Is there frost on the suction line ?    This is usually a sign of either loss of refrigerant charge or most commonly lack of air flow. See the next questions.                                                                                                                                                                                                        Are the filters plugged ?    result will be an extra cold suction line                                                                                                                           Is the evaporator clean ?    result will be an extra cold suction line                                                                                                                          Do you have sufficient air flow ?     result will be an extra cold suction line                                                                                                                   How many air diffusers are closed ?    Too many closed will result with extra cold suction line                                                                                            What is your Supply air temperature ?    Look for a TD of 15 to 20oF                                                                                                              Is the outdoor air temperature too low for proper operation ? Install head pressure controls if you require low ambient operation                                                                                                                                                                                                                                         


 Compressor Short cycles                                                                                                                                         Thermostat Incorrectly installed?    Supply air is influencing it. or is there a door that shakes it when the door closes.
Is it cycling on overload    Is the compressor overheating ?
Sufficient voltage at the unit ?
  Check charge.   
Is it cycling on low or high pressure See low suction or high head

Is the unit oversized.    check square footage of home


                                                                       Ice or frosted Suction line
Check refrigerant charge    Either an undercharge or over charge can cause this.
Are the filters plugged ?   
Is the evaporator clean ?   
Do you have sufficient air flow ?
How many air diffusers are closed ?    Too many closed will result with extra cold suction line
Is the fan belt broke ?     Look for a TD of 15 to 20oF
Is the outdoor air temperature too low for proper operation     Install head pressure controls if you require low ambient operation

                                                                     Compressor does not start
Check thermostat     Turn fan to the on position if the furnace fan starts go check for power at the condensing unit.
Check disconnect , breaker or fuses.    Replace as required
Check Contactor    If the contactor is pulled in the problem is a line voltage problem. If the contactor is not pulled in the problem is in the low voltage side of the unit. Check to see if the coil is energized.
Check low ambient stat.     If open you can temporarily bypass it.
Check time delay relay    If open you can temporarily bypass it.
Is the low pressure control open ?    See low suction pressure. DO NOT BYPASS
Is the high pressure control open ?    See high head pressure. DO NOT BYPASS
Is the compressor hot ?    Off on overload
Start or run cap shorted, open or blown.    If unit humming check these,
Compressor hums    Start or run cap shorted, open or blown, If seized try a hard start kit. do not call compressor if it is hot. Only call a cold compressor


                                                                       Compressor runs non stop
Check refrigerant charge    Either an undercharge or over charge can cause this.
Is the condenser restricted ?    Look for leaves, paper ect.
Is the condenser clean ?    Clean it out with a garden hose. TURN OFF POWER FIRST. to clean it spray the water through the fins in the condenser.
Is there frost on the suction line ?    This is usually a sign of either loss of refrigerant charge or most commonly lack of air flow. See the next questions.
Are the filters plugged ?    result will be an extra cold suction line and low back pressure.
Is the evaporator clean ?    result will be an extra cold suction line and low back pressure.
Do you have sufficient air flow ?     result will be an extra cold suction line and low back pressure.
How many air diffusers are closed ?    Too many closed will result with extra cold suction line and low back pressure.
What is your Supply air temperature ?    Look for a TD of 15 to 20oF
Are the low and high side the same pressure     Cycle unit and to verify that the high pressure internal relief valve is not causing the problem prior to calling the compressor.
Is the compressors drawing RLA ( rated load amps) or less ?  If it's less are valves ok ? look for low head and higher than normal back pressure.

Trouble shooting          Trouble shooting single phase motors         Troubleshooting three phase motors
 

Make a Free Website with Yola.